Document Type
Article
Source Publication Title
The 21st ACM Conference on Embedded Networked Sensor Systems
DOI
https://dl.acm.org/doi/10.1145/3625687.3625801
Abstract
Server-level power monitoring in data centers can significantly contribute to its efficient management. Nevertheless, due to the cost of a dedicated power meter for each server, most data center power management only focuses on UPS or cluster-level power monitoring. In this paper, we propose a low-cost novel power monitoring approach that uses only one sensor to extract power consumption information of all servers. We utilize the conducted electromagnetic interference (EMI) of server power supplies to measure their power consumption from non-intrusive single-point voltage measurements. We present a theoretical characterization of conducted EMI generation in server power supply and its propagation through the data center power network. Using a set of ten commercial-grade servers (six Dell PowerEdge and four Lenovo ThinkSystem), we demonstrate that our approach can estimate each server’s power consumption with less than ∼7% mean absolute error.
Publication Date
4-26-2024
Language
English
License

This work is licensed under a Creative Commons Attribution 4.0 International License.
Recommended Citation
Gupta, Pranjol Sen; Talukder, Zahidur; Abir, Tasnim Azad; Islam, Mohammad A.; and Nguyen, Phuc, "Enabling Low-Cost Server Level Power Monitoring in Data Centers Using Conducted EMI" (2024). Association of Computing Machinery Open Access Agreement Publications-Archive. 86.