Abstract

An increase in utility of internet-based services, cloud computing and greater performance demands due to rising AI and ML applications have led to a steep growth in GPU and CPU thermal design power. Efficient thermal management of these processors has become a bottleneck in performance enhancement and corresponding power densification of these components. Furthermore, increased pressure on data center owners to reduce power demands and move towards green computing has exacerbated the data center cooling challenges. Single-phase immersion cooling allows data center owners to not only dissipate the increasing heat fluxes efficiently but can also potentially improve equipment reliability as the component are no longer exposed to air, humidity, and airborne contaminants. As a part of thermal design considerations when moving from air to immersion cooling, using optimized heat sinks designed for immersion systems plays a key role in obtaining optimal thermal performance from the CPU or GPU components. An in-depth study of designing such an optimized heat sink is addressed in this investigation. A baseline heat sink solution for an air-cooled Open Compute server was numerically optimized using multi-parametric and multi-objective optimizations. The thermal resistance of the heat sink and pumping power of the system were used as objective functions to obtain a heat sink design by tandem optimization of the fin parameters using optiSLang. The optimizations were carried out under both forced and natural convection flow regimes. Also, a comparison of the difference in optimized geometry of the heat sink was carried out for aluminum and copper as fin material. The final optimized heat sinks were used to gauge the percentage improvement in thermal performance and reduction in pumping power as compared to the baseline simulations that use an air-cooled heat sink.

Keywords

Single-phase immersion cooling, optiSLang

Disciplines

Aerospace Engineering | Engineering | Mechanical Engineering

Comments

Degree granted by The University of Texas at Arlington

31376-2.zip (3894 kB)

Share

COinS
 
 

To view the content in your browser, please download Adobe Reader or, alternately,
you may Download the file to your hard drive.

NOTE: The latest versions of Adobe Reader do not support viewing PDF files within Firefox on Mac OS and if you are using a modern (Intel) Mac, there is no official plugin for viewing PDF files within the browser window.