Data center cooling is becoming important to maintain environmental condition for ITE- Information technology equipment. Conventional evaporative wet cooling media lowers the temperature of the dry bulb temperature of incoming air in which heat transfer to water film and sensibly cool the product air by increasing moisture into air. Wet cooling media technique requires large quantity of clean water, which is reducing area where water is very less. Therefore, indirect evaporative cooling is good alternative. Chiller plants/Indirect Evaporative cooling(IEC) are used as a cooling source for larger data centers as they are more efficient in heat transfer without adding moisture into product air. In this study, Chilled water is supplied to the heat exchanger unit ASC- 8 row copper coils indirect heat exchanger. Hot air stream across the coils transfer heat energy to the chilled water inside the coil and excessive moisture in secondary air will be condensed before the outlet as it will reach to the dew point. Focus of this study is to identify the various configurations for cooling coils. Parametric study has been carried out to show the impact of both water and air velocities on coil performance. Variable primary flow of water in chilled water cooling unit has been studied to improve efficiency with reducing pumping power. Weather bin analysis of DFW area for several months has been done. Optimization of coil design has been studied by maintaining balance with coil face area, air pressure drop, and water pressure drop parameters. Numerical simulation data has been validated with Aztek indirect evaporative cooling unit.

Keywords

CFD, Parametric study, IEC, DEC, ITE, ASC-8 row cooling coils

Disciplines

Aerospace Engineering | Engineering | Mechanical Engineering

Comments

Degree granted by The University of Texas at Arlington

26414-2.zip (2244 kB)

Share

COinS
 
 

To view the content in your browser, please download Adobe Reader or, alternately,
you may Download the file to your hard drive.

NOTE: The latest versions of Adobe Reader do not support viewing PDF files within Firefox on Mac OS and if you are using a modern (Intel) Mac, there is no official plugin for viewing PDF files within the browser window.